Function of jumper wires
Name Function
J1(SW5-1)
With 1 Phase model
None 3 Phase model
J2(SW5-2)
With Cooling only type
None Heat pump type
J3(SW5-3)
With Pulse input
None Step input
J4(SW4-1)
With
None
J5(SW4-2)
With Antifrost 2.5˚C
None Antifrost 1˚C
J6(SW4-3)
With With abnormality resetting
None Without abnormality resetting
J7(SW4-4)
With
4 position louver control: valid
None
4 position louver control: invalid
*1 With
FDKN208 type
J7(SW4-4) None
FDKN258, 308 type
Function of DIP switched (SW3)
Switch Function
SW3-1
ON Power off guaranteed
OFF No power off guaranteed
ON With low-voltage detection
control
SW3-2
OFF Without low-voltage detection
control
SW3-3
ON Power up mode (UHi-Lo)
OFF Mild mode (Hi-Lo)
ON Indoor fan is Lo when heating
thermostat is OFF.
SW3-4
OFF Indoor fan is OFF when
heating thermostat is OFF.
Note (1) *1 J7 (SW4-4) is for switching models on the FDKN (P) Series.
Model: FDT, FDR, FDU, FDFL series
Function of DIP switched (SW3)
Switch Function
SW3-1
ON Power off guaranteed
OFF No power off guaranteed
ON With low-voltage detection
control
SW3-2
OFF Without low-voltage detection
control
SW3-3
ON Power up mode (UHi-Lo)
OFF Mild mode (Hi-Lo)
ON Indoor fan is Lo when heating
thermostat is OFF.
SW3-4
OFF Indoor fan is OFF when
heating thermostat is OFF.
(ii) Please match the settings of control switching switches (SW3, SW4, SW5) to the settings they had before they were replaced. With
these switches, if the printed circuit had a jumper wire before being replaced, set to jumper wire ON if there was a jumper wire and
jumper OFF is these was not.
(iii) Connect the fast-on terminals and connectors that are to the circuit board for the micro-computer.
Connect by matching the wire color of the fast-on terminal with the color printed on the circuit board for the micro-computer.
Note (1) When connecting to the fast-on connection for the circuit board for the micro-computer, use care so as not to excessively
distort the circuit board.
Power supply connector
for PCB
Transformer, secondary side External input /
output function
SW4
SW5
SW3
SW1
SW2 (Only case of FDT)
(Optional : For auto lift panel)
( )
Indoor unit number
address switch
( )
For test mode selection
(Shortcircuit : Test mode)
Thermistor
(Return air)
Thermistor
(Heat exchanger)
Transformer, primary side
Power
supply
52X6
52X5 52X4 52X7 52X1 52X2 52X3
CNTCNV
SW4
SW2
SW5
CNE
CNQCNS CNHCNN
SW3
9
1011
76 3 48 13
SW1
Function of DIP switched (SW4, 5)
Switch Function
SW4-1(J1)
ON Antifrost 2.5˚C
OFF Antifrost 1˚C
SW4-2(J2)
ON With abnormality resetting
OFF Without abnormality resetting
SW4-3(J3)
ON 4 position louver control: valid
OFF 4 position louver control: invalid
SW5-1(J4)
ON 1 Phase model
OFF 3 Phase model
SW5-2(J5)
ON Step input
OFF Pulse input
Page view 22