Manual No. '07·PAC-T-115
T E C H N I C A L M A N U A L
C o l l e c t i o n d a t a
PACKAGED AIR-CONDITIONER
MULTI-TYPE (V-MULTI)
PACKAGED AIR-CONDITIONER
(Split system, Air to air heat pump type)
CEILING RECESSED COMPACT TYPE
CEILING RECESSED TYPE
WALL MOUNTED TYPE
CEILING SUSPENDED TYPE
FDTCVA151HEN1R
201HEN1R
(OUTDOOR UNIT)
FDCVA302HENR
402HENAR
402HESAR
502HENAR
502HESAR
602HENAR
602HESAR
802HESAR
1002HESAR
FDTA151R
201R
251R
301R
401R
501R
(INDOOR UNIT)
FDTCA151R
201R
FDTCVA302HENP1R
402HENP2R
402HESP2R
FDTCVA602HENT2R
602HEST2R
FDTVA151HEN1R
201HEN1R
251HEN1R
302HEN1R
402HEN2R
402HES2R
502HEN2R
502HES2R
602HEN2R
602HES2R
FDTVA302HENP1R
402HENP2R
402HESP2R
502HENP2R
502HESP2R
602HENP2R
602HESP2R
802HESP2R
1002HESP2R
FDTVA602HENT2R
602HEST2R
802HEST2R
FDTVA802HESD2R
1002HESD2R
FDKNVA151HEN1R
201HEN1R
251HEN1R
FDKNVA302HENP1R
402HENP2R
402HESP2R
502HENP2R
502HESP2R
FDKNVA602HENT2R
602HEST2R
FDENVA151HEN1R
201HEN1R
251HEN1R
302HEN1R
402HEN2R
402HES2R
502HEN2R
502HES2R
602HEN2R
602HES2R
FDENVA302HENP1R
402HENP2R
402HESP2R
502HENP2R
502HESP2R
602HENP2R
602HESP2R
802HESP2R
1002HESP2R
FDENVA602HENT2R
602HEST2R
802HEST2R
SATELLITE DUCTED TYPE
FDUMVA201HEN2R
251HEN2R
302HEN2R
402HEN2R
402HES2R
502HEN2R
502HES2R
602HEN2R
602HES2R
FDUMVA402HENP2R
402HESP2R
502HENP2R
502HESP2R
602HENP2R
602HESP2R
802HESP2R
1002HESP2R
FDUMVA602HENT2R
602HEST2R
802HEST2R
FDEN
A
151R
201R
251R
301R
401R
501R
FDKNA151R
201R
251R
FDUMA202R
252R
302R
402R
502R
HIGH STATIC PRESSURE DUCT TYPE
FDUVA802HES2R
1002HES2R
updated 3,October,2008
Page view 0
1 2 3 4 5 6 ... 328 329

Summary of Contents

Page 1

Manual No. '07·PAC-T-115T E C H N I C A L M A N U A LC o l l e c t i o n d a t aPACKAGED AIR-CONDITIONERMULTI-TYPE (V-MULTI)PACKAGED AIR-COND

Page 2 - Models FDUMA252R, 302R

- 9 -Model FDTCVA402HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTCVA402HESP2RFDTCA201R FDCVA402HESARNominal cooling capacity(1) kW1

Page 3 - Models FDUMA402R, 502R, 602R

- 99 -Models FDUMA252R, 302R69Space for installation and service6201006001300458604559200130165 285950285 2154655108063540546035149274299199VIEW B295

Page 4 - Models FDUA801R, 1001R

- 100 -Models FDUMA402R, 502R, 602RUnit : mm69ASpace for installation and service1406 (Suspension bolts pitch)VIEW AVIEW BLiquid pipingø9.52(3/8"

Page 5 - Models FDENA251R, 301R

- 101 -830794 (Suspension bolts pitch)Liquid piping801: φ9.52 (3/8")1001: φ12.7 (1/2")φ25.4 (1")Space for installation and serviceAHole

Page 6 - (f) Wall mounted type (FDKN)

- 102 -Air supply(M8 to M10×4pcs.Not included)103001505751101353084040 9901071732102152424690195235271531095268410135105314576φ6.35(1/4")φ12.7(1/

Page 7 - Model FDKNA251R

- 103 -6841069076751101353083001001505154016204024135250 52551734024145271235109531955210531572(Suspension bolts pitch)290(Suspension bolts pitch)φ9.5

Page 8 - (a) Wired remote controller

- 104 -Model FDKNA251RUnit : mmServicespaceServicespaceSpace for installation and serviceormoreormoreor moreormore401510050Installation position diag

Page 9 - Unit: mm

- 105 -(2) Remote controller (Optional parts)(a) Wired remote controllerUnit : mm(This side is not grounded)Earth wiringRemote control switchRemote

Page 10 - ( )

- 106 -6017150(b) Wireless remote controllerUnit: mm

Page 11

- 107 -Liquid piping: φ6.35 (1/4")(Flare connecting)Gas piping: φ12.7 (1/2")(Flare connecting)Piping, wiring outletL2L1L3Terminal blockHoles

Page 12 - (c) Triple type

- 108 -Liquid piping: φ6.35 (1/4")(Flare connecting)Gas piping: φ15.88 (5/8")(Flare connecting)Piping, wiring outletL2L1L3Terminal blockHole

Page 13

- 10 -(c) Triple typeModel FDTCVA602HENT2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDTCVA602HENT2RFDTCA201R FDCVA602HENARNominal cooling

Page 14 - ( )

- 109 -Model FDCVA302HENRUnit: mmL2L1L3L4 Air inletAir outletMaintenancespaceAir inlet( )3801924103.5 48.558088041834088150 1502732Hol

Page 15

- 110 -(φ20×3 pcs.)(M10×4 pcs.)Unit : mmAMinimum allowable space to the obstaclesL1L2L3Air outletAir inletAir inletMaintenancespaceL451403610084510110

Page 16

- 111 -Model FDCVA802HESARUnit: mmTerminal block1300105515509705062557630615585355227 5017050 855015 505016070370410 202040 405560262 38838580190 2001

Page 17 - 1.2.4 Inside view

- 112 -Model FDCVA1002HESARUnit: mmMinimum allowable space to the obstaclesL1L2L3Air outletAir inletAir inletMaintenancespaceL4MarkInstallation

Page 18 - Model FDCVA802HESAR

- 113 -1.2.4 Inside view(1) Outdoor unitModels FDCVA151HENR, 201HENR, 251HENR Model FDCVA302HENRControl boxElectronic expansionvalveReceiver4-way va

Page 19 - Model FDCVA1002HESAR

- 114 -Control boxSolenoid valveLower pressure sensor(LPT)Service valveService valve(Liquid side)(Gas side)CompressorHigh pressure switch(63H1)Electro

Page 20 - 1.2.5 Exterior appearance

- 115 -Model FDCVA1002HESARControl boxSolenoid valveLower pressure sensor(LPT)Service valveService valve(Liquid side)(Gas side)CompressorHigh pressur

Page 21 - Cool white

- 116 -Plaster whitePlaster whitePlaster whitePlaster white(Front panel)(Front panel)(Side panel)(Vertical louver)(Horizontal louver)Light grayLight g

Page 22 - Polar white

- 117 -Stucco white(2) Outdoor unitModels FDCVA151HENR, 201HENR, 251HENR Model FDCVA302HENRCool white(d) Wall mounted type (FDKN)(e) Satellite duc

Page 23

- 118 -Model FDCVA1002HESARPolar white

Page 24 - 1.2.6 Piping system

- 11 -Model FDTCVA602HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDTCVA602HEST2RFDTCA201R FDCVA602HESARNominal cooling capacity(1) kW

Page 25

- 119 -1.2.6 Piping system(1) Single typeModels 152, 202, 252Indoor unit Outdoor unitThermistor(ThI-R2)Thermistor(ThI-R1)Thermistor(ThO-D)Thermistor(

Page 26 - Outdoor unit

- 120 -Indoor unit Outdoor unitThermistor(ThI-R2)Thermistor(ThI-R1)Thermistor(ThO-D)Thermistor(ThO-S)Thermistor(ThO-A)Cooling cycle Heating cycleTherm

Page 27

- 121 -Models 402, 502, 602((Indoor unitIndoor unit Outdoor unitThermistor(ThI-R2)Flare connectingDiameter jointof different(15~25 only)Flare connect

Page 28 - Model 802

- 122 -Models 802, 1002Indoor unitIndoor unitOutdoor unitThermistor(ThI-R2)Thermistor(ThI-R1)Thermistor(ThI-A)Thermistor(ThO-S)Thermistor(ThO-H)Therm

Page 29 - ( )

- 123 -Model 802Heat exchangerFlare connectingLiquid branch pipe(φ9.52)Flare connecting(φ15.88)Gas branch pipeIndoor unitIndoor unitIndoor unitOutdoo

Page 30

- 124 -(4) Double twin typeModels 802, 1002Flare connecting(φ6.35)Flare connecting(φ6.35)Diameter jointof differentDiameter jointof differentIndoor

Page 31 - 1.2.7 Selection chart

- 125 -Preset point of the protective devicesParts name MarkEquippedunit152, 202, 252 model 302, 402, 502, 602 model 802, 1002 modelThermistor(for pro

Page 32

- 126 -1.2.7 Selection chartCorrect the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacit

Page 33 - Indoor air temperature (˚CDB)

- 127 -0.400.500.600.700.800.901.001.101.201.301.40-15 -13 -9 -5 -1 3 7 11 15 19 23 3127 35 39 43Capacity compensation coeffcientCapacity compensation

Page 34 - Model FDTVA151HEN1R

- 128 -0.600.700.800.901.001.101.201.30-15 -13 -9 -5 -1 3 7 1511 19 23 27 31 35 39 43Capacity compensation coeffcientAmbient air temperature (˚CDB)Ind

Page 35 - Models FDCVA802,1002

- 12 -(2) Ceiling recessed type (FDT)(a) Single typeModel FDTVA151HEN1RModelItemFDTVA151HEN1RFDTA151R FDCVA151HENRNominal cooling capacity(1) kW4.0

Page 36

- 129 -Indoor air temperature (˚CD.B)Capacity compensation coeffcientAmbient air temperature 10˚CW.BAmbient air temperature 18.5˚CW.BAmbient air tempe

Page 37

- 130 -0.400.500.600.700.800.901.001.101.201.301.40-15 -13 -9 -5 -1 3 1171519233127 35 39 43Ambient air temperature (˚CDB)Ambient air temperature (˚CD

Page 38

- 131 -0.300.400.500.600.700.800.901.001.10-13-15 -9 -5 -1 3 7 11 15 19 23 27 31 35 39 43Ambient air temperature (˚CDB)Power consumption correction fa

Page 40 - Sensible heat factor

- 133 -0.600.650.700.750.800.850.900.951.001.05-15 -13 -9 -5 -1 3 11715192723 31 35 39 43Ambient air temperature (˚CDB)Ambient air temperature (˚CDB)S

Page 41

- 134 -0.500.600.700.800.901.001.10-15 -13 -9 -5 -1 3 7 11 15 19 23 27 31 35 39 43Ambient air temperature (˚CDB)Sensible heat factorIndoor airtemperat

Page 42

- 135 -(ii) Models 302 ~ 602 Ambient air temperature 5°C or more550.9880.933 0.8700.8240.8100.979 0.9630.9410.93540 45 500.9930.954 0.9100.8780.868

Page 43 - Static pressure (Pa)

- 136 - Ambient air temperature -5°CEquivalent piping length(1) (m)CoolingHeating7.5 10 15 20 25 30 35 40 45 50 5511 0.993 0.979 0.965 0.950 0.936 0.

Page 44 - Standard·High

- 137 -1.2.8 Characteristics of fan(2) Satellite ducted type (FDUM)3-spot blowerinternal resistanceStandardHighStandardMediumStandard LowSquare duc

Page 45 - Model FDTVA201HEN1R

- 138 - 21 25 28 31100120806040200-10FDUMA302R FDUMA402R100120806040200-1014 17 20 22Air flow(m3/min)LowerlimitUpperlimit[Standard] 3-sp

Page 46

- 13 -Model FDTVA201HEN1RModelItemFDTVA201HEN1RFDTA201R FDCVA201HENRNominal cooling capacity(1) kW5.0 [2.2~5.6]Nominal heating capacity(1) kW5.4 [2.5

Page 47 - 1.2.9 Noise level

- 139 -200 20015010050015010050038 40 4550 5560 65 51 55 60 65 70 75 80 85 87HighHigh• Condition of standard ratingLowLow rated air volume: 100Pa• Co

Page 48

- 140 -1.2.9 Noise levelNotes (1) The data are based on the following conditions.Ambient air temperature: Indoor unit 27˚C DB, 19˚C WB. Outdoor unit

Page 49 - (standard 0.0002µ bar)

- 141 -Models FDENA151R, 201RNoise level 42 dB (A) at HIGH 39 dB (A) at MEDIUM 38 dB (A) at LOWModels FDENA251R, 301RNoise level 44 dB (A) at HI

Page 50

- 142 -N30N40N20N50N60N7063 125 250 500 1000 2000 4000 8000203040506070203040506070Souud Pressure Level (standard 0.0002µ bar)Mid Octave Band Frequen

Page 51 - 1.3 ELECTRICAL DATA

- 143 -(2) Outdoor unitMeasured based on JIS B 8616Mike position: at highest noise level in position as mentined belowDistance from front side 1mHeig

Page 52 - Hi CEILING SET STANDARD

- 144 -Thermo ON output(DC12V output)Inspection output(DC12V output)Remote operation input(volt-free contact)Auxiliary relay(For DM)Terminal block(

Page 53 - Model FDTA501R, 601R

- 145 -Remote operation input(volt-free contact)Auxiliary relay(For FM)Auxiliary relay(For DM)Terminal block( mark)Connector( mark)Closed-end co

Page 54 - Wired specification

- 146 -132/NRDBLBLRDRDWHWHWHWHCnW1TBCnW4TrI220/240V15VPower boardPrinted circuitboardF(3.15A)F(0.16A)BKBKBKBKBKBKCnN3CnN4CnN1CnHCnTXR1 XR3XR2 XR4XR5Th

Page 55 - Models All models

- 147 -F (3.15A)Remote controllerXCnB CnB2 AMP SW2 SW1LED3 LED1 LED2ZYTB*1CFI2 CnF2FMI2 CFI1 FMI1 CnF1CnRCnM3CnI 12/NWHRDWHBRBKBLRDBKBKBKB

Page 56 - Model FDTVA251HEN1R

- 148 -CFMI1,2CFI1,2DMFSThI-AThI-R1ThI-R2ThCFan motorCapacitor for FMIDrain motorFloat switchThermistorThermistorThermistorThermistorSW5-3,4SW9-3TrIFL

Page 57

- 14 -Model FDTVA251HEN1RModelItemFDTVA251HEN1RFDTA251R FDCVA251HENRNominal cooling capacity(1) kW5.6 [2.8~6.3]Nominal heating capacity(1) kW6.7 [3.1

Page 58 - Wireless specification

- 149 -Printed circuitboardUHOption852FH7CCnM313852FL7HML57 9XR2Option654XR4XR5XR3CnT321XR112V12V123413533554466I2I1ThCRDRemote controllerBKWHCnB123TB

Page 59 - Outdoor swith board

- 150 -to outdoor unitPower lineSignal line132/NWireless specificationWired specificationRemote controllerRemote controllerThCXXCnBZYZYTB1FMI SWLED5LE

Page 60

- 151 -Printed circuit boardSub printed circuit boardPosition of compressor terminalsBKWRDUWHVTo indoor unitPower wiresSignal wire1321Phase220-240V 5

Page 61

- 152 -Model FDCVA302HENRYellow/GreenColorWH WhiteGRYY/GNGrayP PinkYellowMarkColor marksBRORRDBKBLRedOrangeBrownBlueBlackAuxiliary relay (for 20S)Exp

Page 62

- 153 -Models FDCVA402HENAR, 502HENAR, 602HENARYellow/GreenColorWH WhiteGRPYY/GNGrayPinkYellowMarkColor marksBRORRDBKBLRedOrangeBrownBlueBlackt˚t˚t˚t

Page 63

- 154 -t˚ t˚ t˚ t˚ t˚Position of compressor terminalsAuxiliary relay(for 20S)Expansion valve for coolingSolenoid valve for 4 way valveAuxiliary relay(

Page 64

- 155 -t˚t˚t˚t˚t˚t˚CMBLRDIPMInverterPWB2DMRDN2P2P3PUNL1BLBKGN-6RD+4R5AC1BKRDRDL1oL1iTBBKBLWHRDRDNL3L2L152X6MS3~BLWHVWPWB4BLAC3AC252XDC FANCNW1CNA2BLCN

Page 65 - Operation section

- 156 -1.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER(1) Remote controller(a) Wired remote controllerThe fi gure below shows the remote controller

Page 66

- 157 -(b) Wireless remote controllerIndication sectionFAN SPEED indicator Indicates the selected blow rate.ON-TIMER indicator Indicated when ON-TI

Page 67 - Model FDTVA302HEN1R

- 158 -(c) Control parts operation during cooling and heatingFunctionControl partCooling Fan Heating DryThermostatONThermostatOFF–ThermostatONThermos

Page 68

- 15 -Model FDTVA302HEN1RModelItemFDTVA302HEN1RFDTA301R FDCVA302HENRNominal cooling capacity(1) kW7.1[3.9~8.0]Nominal heating capacity(1) kW8.0[4.0~9

Page 69 - ×: Not possible

- 159 -(d) Dehumidifying operation (“THERMAL DRY”)The compressor, the indoor fan motor and the outdoor fan motor are operated intermittently under th

Page 70 - Room temperature (deg)

- 160 -4) Weekly Timer Each day, it is possible to set this timer’s operation up to 4 times (On timer, or Off timer).5) Possible joint use timer op

Page 71

- 161 -SW5-3 OFFSW5-4 OFFSW5-3 OFFSW5-4 ONSW5-3 ONSW5-4 OFFSW5-3 ONSW5-4 ONSetting time: 180 hrs. (when shipped from factory)Setting time: 600 hrs. (D

Page 72 - SW5 setting

- 162 -(k) Condensate pump motor (DM) Control [FDT and FDUM models only](a) Drain motor is started no sooner than the compressor is turned ON durin

Page 73 - Air Conditioner B

- 163 -(q) Using 1 remote controller to control multiple units (indoor units - up to 16 units)1) Function A single remote control switch can be used

Page 74 - DRY COOL FAN HEAT AUTO

- 164 - a) At shipping from factory J1 (SW7-1) on PCB is closed (ON). • Input signal to CnT OFF ON [Edge input] ... Air conditioner ON • Input

Page 75

- 165 -DRY COOL FAN HEAT AUTO(3) Operation control function by the wired remote controller(a) Remote controller operation mode switch switching sequ

Page 76

- 166 -ModelItemUnits: rpsOutdoor unitMaximum required speedMinimum required speed20195[90](2)3015175(70)(1)3025112540(4) Operation control function

Page 77 - Ambient air temperature (˚C

- 167 -3) Compressor protective start IIIWhen the following conditions are satisfi ed, compressor start III is implemented. a) Less than 6 hours have

Page 78 - Model FDTVA402HEN2R

- 168 -3) When the compressor is ON and if the outdoor fan speed is 75 rpm or lower for 30 seconds or longer, the compressor is stopped immediately.

Page 79 - The compressor speed is

- 16 -Model FDTVA402HEN2RModelItemFDTVA402HEN2R (5)FDTA401R FDCVA402HENARNominal cooling capacity(1) kW10.0 [6.1~11.2]Nominal heating capacity(1) kW1

Page 80 - Compressor stops

- 169 -2) Procedure to change defrosting start conditionTurn SW5-1 on the outdoor unit PCB ON.a) When cumulative operating time of compressor elapse

Page 81

- 170 -2) Anomalous discharge pipe temperaturea) If the discharge pipe temperature rises to 105°C or higher, the compressor is stopped [the outdoor

Page 82

- 171 -(h) Inverter protection control 1) Current cut controlThis prevents overcurrent at the inverter. If the current exceeds the set value, the co

Page 83

- 172 -ModelItemUnits: rps402 502 602 802 1002Outdoor unitMaximum required speedMinimum required speed904030295 2010540115401003012030ModelItemUnits:

Page 84

- 173 - b) After starting for 30 seconds, the compressor will run at fi xed frequency within 2~4 minutes with Brps as the target speed.Model Operation

Page 85

- 174 -(d) Outdoor unit fan control(i) Contents of fan speed controlFM01870 790(820) 740 600 400 200FM01FM01FM01FM01910 850 820 560 370 200FM02910 8

Page 86 - Ambient air temperature (˚C)

- 175 -(ii) Fan speed control when the unit started1) During heating and defrosting fan controla) The outdoor unit’s fan is started in 4th speed sim

Page 87 - Outdoor unit fan speed

- 176 -A60 70 85 90 70 9070 7085 90 70 9080 72 72 80 80 8075 68 68 75 75 75BCDModelItem30240250260280210024) Cautions concerning outdoor unit fan sta

Page 88 - PSL Detecting

- 177 -(e) Outdoor unit fan control during cooling when the outdoor air temperature is low(i) When cooling or dehumidifying, if the ambient air temp

Page 89 - Model FDTVA402HES2R

- 178 --20-25-23-21-17-15-10-5-2-15 -10 -5 0 5 6 10-20-23-20-25-30-24-15-10-8-15 -10 -5 0 5 6 10-20-23Outdoor heat exchanger temperature (˚C) [Tho-R]S

Page 90 - Compressor operation

- 17 -Model FDTVA402HES2RModelItemFDTVA402HES2R (5)FDTA401R FDCVA402HESARNominal cooling capacity(1) kW10.0 [6.1~11.2]Nominal heating capacity(1) kW1

Page 91

- 179 -(iii) Defrosting end conditions If any of the following conditions is satisfi ed, the defrosting operation fi nishes.1) 8 minutes and 20 secon

Page 92 - Indoor heat exchanger

- 180 -(iii) Current safe control1) If the inverter primary current (CT current) becomes higher than the following set value, the compressor speed i

Page 93

- 181 -2) Low pressure error detectiona) If either of the following conditions is satisfi ed, the compressor is stopped. If the low pressure is 0.0

Page 94

- 182 - Outdoor heat exchanger thermistor : -50°C or lower Ambient air temperature thermistor : -30°C or lower Low pressure sensor: 0 V or lower

Page 95 - SAFETY PRECAUTIONS

- 183 -(m) Pump down controlIf the pump down button SW1 (SW9) is kept on pressing for 2 seconds during an operation stop and anomalous stop (not incl

Page 96 - Obstacle

- 184 -1.5 APPLICATION DATASAFETY PRECAUTIONS• Please read these “Safety Precautions” fi rst then accurately execute the installation work.• Though t

Page 97 - Control box

- 185 -1.5.1 Installation of indoor unit(1) Ceiling recessed compact type (FDTC)(a) Selection of installation location1) Select location where the

Page 98 - Drain socket

- 186 -Drain socketClamp(accessory)No adhesive allowedPipe cover (large)[for insuation](accessory)Joint for VP-25(not included)Drain hose piece(access

Page 99 - [Figure 3]

- 187 -Drainage test Check that water is draining thoroghly during test run, and that there are no water leaks from the joints and the drain pan.

Page 100 - Model FDTAV502HEN2R

- 188 -♦ Setup from a remote controller side.Drain pump operation from a recomte controller unit is possible. Operate a remote controller unit by foll

Page 101 - [Figure 7]

- 18 -Model FDTAV502HEN2RModelItemFDTVA502HEN2RFDTA501R FDCVA502HENARNominal cooling capacity(1) kW12.5 [6.5~14.0]Nominal heating capacity(1) kW14.0

Page 102 - 1‚000 or more

- 189 -[Figure 5][Figure 4]BAA7) A panel is hooked on two bolts ( mark ) [Figure 4]8) Please rotate a hook, put in the slot on the panel, and carr

Page 103

- 190 -(2) Ceiling recessed type (FDT)(a) Selection of installation location1) Select location where the space above ceiling is larger than those m

Page 104 - Drain plug

- 191 -(c) Suspension• Please arrange four sets of a suspension bolt (M10 or M8), a nut matching the bolt, a fl at washers and a spring washer on the

Page 105 - 33~38 mm

- 192 -b) Give the drain piping a descending grade (1/50-1/100) and never create a bump to go over or a trap. c) In connecting drain pipes, care mus

Page 106 - Corner panel

- 193 -♦ Setup from a remote controller side.Drain pump operation from a remote controller unit is possible. Operate a remote controller unit by follo

Page 107 - Air supply (small)

- 194 -ScrewCorner panelDirt collectsAir leakage at ceilingAir leakageCondensation forms, condensation dripsAdjust so there is no gap.4) Removing the

Page 108 - FDENA401R, 501R, 601R

- 195 -Drain plugAir supply (small)StrikerDrain pipingAir screenAir supply (small)RefrigerantpipingScrew1 241 233LouverLouver motorLLConnectorLouver m

Page 109 - Side panel screw

- 196 -FDENA151R, 201R FDENA251R, 301RFDENA401R, 501R, 601RPinPinScrewClawsAa8) Corner panel installation Hook the corner panel strap to the pin on

Page 110 - Air supply

- 197 -Side panelSide panel screw (1 each on the left and right sides) (M4)(c) Installation preparation1) Remove the air return grille.Slide the stop

Page 111 - TABLE OF CONTENTS

- 198 -4) Suspension bolt positiona) Using the paper pattern supplied as an accessory as a criterion, select suspension bolt positions and piping ho

Page 112 - Model FDTAV502HES2R

- 1 -TABLE OF CONTENTS1. PACKAGED AIR-CONDITIONER ...22. MULTI-TYPE (

Page 113

- 19 -Model FDTAV502HES2RModelItemFDTVA502HES2RFDTA501R FDCVA502HESARNominal cooling capacity(1) kW12.5 [6.5~14.0]Nominal heating capacity(1) kW14.0

Page 114 - 50 or more

- 199 -(e) Refrigerant piping1) Piping position2) Piping connection positionPiping can be connection from 3 different directions. Remove the cutout f

Page 115

- 200 -Use the fitting supplied with the unit to connect the drain hose, fastening it at the lowest point so that there is no slack, and establishing

Page 116

- 201 -Reference holeWARNING Level matching mark 450Unit: mmLeveling Plates3) Adjust the level of mounting plate under the condition that four screws

Page 117 - Concrete

- 202 -1. Remove the drain hose. 2. Remove the drain cap. 3. Insert the drain cap. 4. Connect the drain hose.b) Procedure for changing drain hose•

Page 118 - Hi CEILING SET Hi CEILING 1

- 203 -(5) Satellite ducted type (FDUM)(i) Selection of installation location1) Avoid installation and use at those places listed below.a) Places

Page 119 - Supply ai

- 204 -2) Adjusting the unit’s levelnessa) Adjust the out-levelness using a level vial or by the following method.• Make adjustment so that the rel

Page 120 - Bad example of duct work

- 205 - Return air port• When shipped, the return air port lies on the back.• When connecting the duct to the return air port, remove the air filt

Page 121 - Joints for VP-25

- 206 -• There is a possibility that the supply air volume may exceed the allowable range of operation due to the capacity of ventilation fan or stre

Page 122 - CnR (2P Blue)

- 207 -Joint for VP-25(local procurement)Pipe cover (small)[insulation](accessory)Drain socketIndoorunitClamp(accessory)Drain hose(accessory)AdhesionV

Page 123 - Model FDTVA602HEN2R

- 208 - Forced drain pump operation♦ Setup from a unit side.  Turn power on after selecting the emergency operation mode with a setting on the indoo

Page 124 - Front view Top view

- 20 -Model FDTVA602HEN2RModelItemFDTVA602HEN2RFDTA601R FDCVA602HENARNominal cooling capacity(1) kW14.0 [6.7~14.8]Nominal heating capacity(1) kW16.0

Page 125 - Discard them after unpacking

- 209 -Air conditions, limitation of air volumeAir volume (m3/min) Indoor unit suction air temperature801 model 51 38 65RatingLower limit Upper limitC

Page 126 - 2=1/2 H1 or 50 ~ 100 mm

- 210 - If a duct is not provided at the suction side but it is substituted with the space over the ceiling, humidity in the space will increase by

Page 127 - F1(6.3A)

- 211 -4) When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in th

Page 128 - 212(1)

(e) Drain Test When the drain piping work is over, inject water to inspect if the piping is arranged properly or not.

Page 129 - 212(2)

-- 212(1) <Precautions for wiring>4) Installation procedure a) Taking out connectors CnF2 and CnF3 from the protection tubes(Fig.A), disconnect the c

Page 130 - Black wire

-- 212(2) Fig.D Fig.GCapacitorFuseFan controller,M3 tapping screw(2 pcs.)LabelBand aFig.FBracketBracket(fuse)M4 tapping screw(2 pcs.)(Capacitor)(Brac

Page 131 - Heavy Heavy

- 213 -(1) Selection of installation location Avoid the following locations (a) Direct sunlight. (b) Close to heating device. (c) Highly humid o

Page 132 - Notabilia for installation

- 214 -1.5.3 Installation of outdoor unit(1) Haulage and installation (Take particular care in carrying in or moving the unit, and always perform su

Page 133 - Mark Mark Mark

- 215 -L1L2L3L4I100100250DistanceFDCVA151~251 FDCVA302 FDCVA402~100zUnit: mmInstallationexampleAir inletAir outletservice spaceAirinletL1L4L3L2Open sp

Page 134 - Model FDTVA602HES2R

- 216 -Height difference• When the position of outdoor unit is higher than that of the indoor unit, keep the difference H=30 m or less.• When the

Page 135 - < 3-Way Branch >

- 21 -Model FDTVA602HES2RModelItemFDTVA602HES2RFDTA601R FDCVA602HESARNominal cooling capacity(1) kW14.0 [6.7~14.8]Nominal heating capacity(1) kW16.0

Page 136 - (iv) Double twin type

- 217 -< 2-Way Branch >< 3-Way Branch >FloorFloorFloorFloorFloorFloorMount sections level with the floor.Mount sections

Page 137

- 218 - (iv) Double twin typeModels FDCVA802, 1002 [Branch pipe set : DIS-WA1 × 2set, DIS-WB1 × 1set]Outdoor unitIndoor unitDIS-WA1DIS-WA1DIS-WB1Gas

Page 138

- 219 -Do not hold the valve cap area with a spanner.Please use a torque wrench. If a torque wrench is not available, fasten the flare nut manually fi

Page 139 - Inner face of

- 220 -(d) How to remove the side cover • Models FDCVA151 ~ 302First unscrew four screws holding the side cover in place, pull down the cover towa

Page 140 - About brazing

- 221 -Accessory pipe AStraight pipe (Procured in the fieldabove 415mm)Braze the field pipe here.Installation example (Downward)Accessory pipe AStrai

Page 141

- 222 -Straight pipe φ22.2 (OD)to be procured locallyBranching pipe set(DIS-WB1, DIS-TB1)Accessory pipe AElbow to beprocured locallyAccessory pipe BFi

Page 142 - Drain elbow

- 223 -When a vacuum air purge is completed, remove the valve rod cap nuts and open the service valves (both liquid and gas sides) as illustrated belo

Page 143

- 224 -(b) Charging refrigerant1) Since R410A refrigerant must be charged in the liquid phase, you should charge it, keeping the container cylinder u

Page 144

- 225 -4) Between master and slave indoor units, connect between the same numbers , ,  and , , on the respective terminal blocks. Power cable,

Page 145 - (b) Twin type

- 226 -5) Set the same address for the master and slave indoor units as the communications address for the remote controller using rotary switch SW2

Page 146

- 22 -(b) Twin typeModel FDTVA302HENP1R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA302HENP1RFDTA151R FDCVA302HENRNominal cooling capac

Page 147

- 227 -(7) Setting functions using the wired remote controller(a) The default settings of this unit’s functions are as follows: If you want to charg

Page 148 - I/U FUNCTION

- 228 - Indoor unit functions (I/U FUNCTION )010304050607080910Functionnumber ADefaultsettingHi CEILING SETFILTER SIGN SET POSITIONEXTERNAL

Page 149 - STANDARD

- 229 -(b) Function setting method1) Stop the air conditioner2) Press the SET and MODE buttons simultaneously for 3 seconds or longer.The screen di

Page 150

- 230 - When “I/U FUNCTION ” is selected. The screen display will be switched as follows:“ I/U SELECT” “ SET” “I/U No.00” (blinking) Press eith

Page 151

- 231 -(c) Changing the remote control set temperature range1) It is possible to change the set temperature range using the remote control.a) The u

Page 152

- 232 -12Function No. A (Example) If the upper limit is set at 28 ˚CFunction Contents B Setting Contents ˚CTEMP RANGE SETDISP CHANGENO DISP CHANGECont

Page 153

- 233 -Number0102030405071121222324272829313234353637(Operation mode)(Indoor unit heat exchanger temperature 1)(Indoor unit heat exchanger temperature

Page 154

- 234 - Models FDCVA302 ~ 10021) Test run methoda) A test run can be initiated from an outdoor unit by using SW3-3 (SW5-3) and SW3-4 (SW5-4) for

Page 155 - 1.6 MAINTENANCE DATA

- 235 -Valve for a heating operationValve for a cooling operationComplete shut positionWhen power isturned onDuring a cooling operationWhen the unit c

Page 156

- 236 -Indoor unitOutdoor unitGas lineLiquid lineCharge hoseCharge hoseGauge manifoidCharge valveVacuum adapterVacuumpumpHandle LoHandle HiCharge port

Page 157 - A little

- 23 -Model FDTVA402HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA402HENP2R(6)FDTA201R FDCVA402HENARNominal cooling capacity(1) kW

Page 158

- 237 -(2) Refrigerant charging(a) After the evacuation shown in the above, change the connection of the charge hose to the refrigerant cylinder.(b)

Page 159 - 2) Outdoor unit side

- 238 -(1) Selfdiagnosis function(a) Check Indicator TableWhether a failure exists or not on the indoor unit and outdoor unit can be known by the cont

Page 160

- 239 -Outdoor unit LEDIndoor unit LEDGreenKeeps flashingKeeps flashingKeeps flashingKeeps flashingKeeps flashingKeeps flashingKeeps flashingKeeps fla

Page 161

- 240 -Section Display sectionError code of remote controllerInspection LED (red) of indoor unit PCBInspection LED (red) of outdoor unit PCB• Displays

Page 162 - Fan motor

- 241 -4) Recording and reset of errorNotes (1) Priority is in the order of E1 > ... > E10 > ... > E60.(2) Procedures of trouble diag

Page 163

- 242 -Parts layout on the indoor unit PCBModel: FDTC seriesInput signal for CnT - Level inputInput signal for CnT - Pulse inputHeating thermostat OFF

Page 164

- 243 -CNM352X6 52X1 52X2 52X352X452X8-2PC3IC2C2X1CNEF2F1Z2DZ3DZ4DZ5DR16ZD1CNJD2IC7TVS1CNM2CNW8CNTIC9J81234J10J11J12CNRIC12CNG LED2 LED1CNW9C13PC5C12C

Page 165

- 244 -CNW1CNJ2CNM3CNRCNVLED1LED2CNB CNW2KN152X552X352X252X252X652X452X8-252X8-152X7L3F1ZNRCNW0CNM1L2L1C57CNQ CNTCNH CNN1SW2 SW5CNESW8SW7SW9SW10IC8IC7

Page 166

- 245 -Heat exchanger thermistor(Thl-R2)Remote controllerPCB power supplyconnector(Primary side)PCB power supplyconnector(Secondary side)Fan motorConn

Page 167

- 246 -CNTCNVCNOCNHCNFCNBCNQCNN1CNN2SW2 SW10SW5 SW7SW9SW8CNZ CNICNOCNAF3F2CNK2CNK1CNW2CNGCNECNW0CNW1CNM352X352X5 52X452X2 52X1 52X6L3L2L1L4CNJ2 CNRF1L

Page 168

- 24 -Model FDTVA402HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA402HESP2RFDTA201R FDCVA402HESARNominal cooling capacity(1) kW10.

Page 169 - is GND

- 247 -1Error display : No displayLCD display : No display[Power supply line error]Indoor unitRed LEDGreen LEDStays OFFStays OFFRed LEDGreen LEDSt

Page 170

- 248 -Indoor unitGreen LEDRed LED 3 time flashKeeps flashingOutdoor unitGreen LEDRed LED Stays OFFKeeps flashingOKIs thewiring for remotecontroller c

Page 171 - Models 302~1002

- 249 -2Error display “ WAIT ”Indoor – outdoor communications troubleInitial (when the power is turned on)Indoor unitRed LEDGreen LEDStays OFFKeeps f

Page 172

- 250 -YESYESDC approx. 12VNONOYesNO(1)(1)(2)DC approx. 0VNote (1) LED Colors402~602: Yellow LED302, 802, 1002: Green LEDNote (1) Values in ( ) sh

Page 173 - Stays OFF or Lights

- 251 -ItemNo.Wrong connection exampleIndication and 2/N reversing and  reversing 2/N and  reversing, 2/N and , wrongly connected1234512/

Page 174 - Thermistor resistance (kΩ)

- 252 -3Error display : E1[Communication error between the remote controller and the Indoor unit]Indoor unitRed LEDGreen LEDStays OFFKeeps flashi

Page 175 - Indoor unit heat exchan

- 253 -YESYESNONOIs the indoor unit heat exchangerthermistor connectorconnection OK?Correct itAre characteristicsof indoor unit heatexchanger thermist

Page 176

- 254 -7Error display : E9[Drain trouble]Indoor unitRed LEDGreen LED1 time flashKeeps flashingRed LEDGreen LEDStays OFFKeeps flashingOutdoor unitCo

Page 177

- 255 -YESNOAre the settingsbetween the master andslave indoor units good?Modify the master/slave setting.YESNONOIs the wiring for remote controller c

Page 178

- 256 -NONOCheck the operation data by the remote controller.Reset the error code and operate the fan in fan mode with Lo fan speed.Check the circumst

Page 179

- 25 -Model FDTVA502HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA502HENP2RFDTA251R FDCVA502HENARNominal cooling capacity(1) kW12.

Page 180 - Error display :

- 257 -NONOCheck the operation data by the remote controller.Reset the error code and operate the fan in fan mode with Lo fan speed.Check the circumst

Page 181

- 258 -11Error display : E28[Defective remote controller thermistor.]Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LEDGreen LEDStays OFFKeep

Page 182 - Test run operation switch

- 259 -(4) Error diagnosis procedures at the outdoor unit sideAt the error diagnosis related to the outdoor unit, fi rst of all check the error code o

Page 183 - External PCB

- 260 -Outdoor air temp. thermistor,Outdoor heat exchanger thermistor,Discharge pipe thermistor(Tho-A, Tho-R, Tho-D)Fan motorStepping motorDIP switch(

Page 184 - ( )

- 261 -CNPS CNEEV1 CNEEV2 CNFANCNN CNS CNR CNHCNWCNA1CNI3CNIPCNG1 CNAFCNI1CNVCNTHCNW2CNECNJCNQ1CNQ2SW4LED3Fan motorSolenoid valve(SV1)(PSL)(EEVC,EEVH)

Page 185 - Model FDCVA302HENR

- 262 -Solenoid valve(802, 1002 only)Outdoor unitpower supplyCNEEV1 CNEEV2 CNJCNI1CNI3CNVCNI5CNW2F1 250V 2ACNWCNHCNLCNMCNFCNSCNN1CNN2CNRCNA1CNFAN1CNFA

Page 186

- 263 -LED1JSW11 JSW10JSW11Match to the PCB conditionsthat existed before replacement.JSW10Match to the PCB conditionsthat existed before replacement.

Page 187 - Temperature (˚C)

- 264 - Models FDCVA402HESAR, 502HESAR, 602HESAR SW2SW1Match to the PCB conditionsthat existed before replacement.(

Page 188 - Outdoor unit check points

- 265 -LNETBTBRedWhiteY/NGLED1RedT1 T5RedWhiteBlackOrangeYellowUVWT6 T7 T8CMF2 (250V 20A)CnTRControl PCBPower transistor moduleCNI3 T2 T46DC280VF3 (25

Page 189

- 266 -0204060801001201401601802000 20 40 60 80 100 120 140Temperature-resistance characteristics ofA/F thermistor (Tho-AF)Thermistor resistance (kΩ)T

Page 190 - Models FDCVA402~602HENAR

- 26 -Model FDTVA502HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA502HESP2RFDTA251R FDCVA502HESARNominal cooling capacity(1) kW12.

Page 191

- 267 -To indoorunit**0204060801001201401601802000 20406080100120140Temperature-resistance characteristics ofA/F thermistor (Tho-AF)Thermistor resista

Page 192 - Outdoor unit check points

- 268 -L1RedRedWhiteBlueRedWhiteDC295 ~ 339VBlueRedWhiteBlueBlueBlackBlackGreenGreenTBTBL2L3NENoise filterDMControl PCBCMInverter PCB12/N3EL1iL2iL3iNi

Page 193 - Correct it

- 269 -LED1 (Red) CheckFlashing 1 time: Current cut (Power transistor overcurrent)• Short circuit in compressor wiring.• Inverter PCB failure• Power t

Page 194 - Error display :

- 270 -1Error display : E5[Communications error during operation]Indoor unitRed LEDGreen LED2 time flashKeeps flashingRed LEDGreen LED2 time flashKe

Page 195

- 271 -3Error display : E34[Power supply open phase] [Only case of 302~1002 models]Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LEDGreen LE

Page 196

- 272 -4[Cooling overload operation]Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LEDGreen LED1 time flashKeeps flashingOutdoor unitAre the ch

Page 197 - [T≤90˚C]

- 273 -Are thecharacteristics ofthe outdoor heat exchangerthermistornormal?NOYESReplace the outdoor heatexchanger thermistor.Is the unit normal?Check

Page 198

- 274 -Is the discharge pipe ther-mistror characteristicsnormal?YESNONOYESReplace the discharge pipe thermistor.The outdoor unit control PCB is faulty

Page 199

- 275 -6[Defective outdoor unit heat exchanger thermistor]Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LEDGreen LED1 time flash Keeps flashin

Page 200

- 276 -8[Defective discharge pipe thermistor]Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LEDGreen LED1 time flashKeeps flashingOutdoor unitI

Page 201

- 27 -Model FDTVA602HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA602HENP2RFDTA301R FDCVA602HENARNominal cooling capacity(1) kW14.

Page 202

- 277 -10[Power transistor is overheating] [Only case of 402~1002 models] Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LEDGreen LED1 time fla

Page 203

- 278 -Is the powersupply voltageproper?• Is the installation space for the indoor and outdoor units proper?• Is there any short circuit of air flow i

Page 204

- 279 -13Error display : E47[Only case of 151 ~ 251, 302 models] Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LED1 time flashGreen LEDKeeps

Page 205 - Low pressure (MPa)

- 280 -Remove the obstruct.YESYESNOReplace thefan motor.NOIs the unit normal?Replace thefan motor.NOYESNOCheck the powersupply voltage.NOReset the pow

Page 206

- 281 -15Error display : E49[Anomalous low pressure or low pressure sensor disconnection.] Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LED

Page 207

- 282 -YESNOReplace the outdoor unit inverter PCB.Fasten it correctly.Reset the power supply.OccursDoes E51 occur?Are the screws to fix the power tran

Page 208 - Temperature (°C)

- 283 -Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LEDGreen LED1 time flashKeeps flashingOutdoor unitCorrect itNOYESYESNOThe under-dome temp

Page 209 - Inverter

- 284 -20[Power transistor thermistor fault] [Only case of 151~251 models]Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LED1 time flashOutdoor

Page 210 - E60 recurs

- 285 -Indoor unitRed LEDGreen LEDStays OFFKeeps flashingRed LED1 time, 2 time, 3 time flash Outdoor unitNO NONONGYESCheck the power supplyReplace the

Page 211

- 286 -NO (E59)(1)YES YESE59 diagnosis E42 diagnosisCheck the compressorIt doesn’trecur.E60 recurs.Does the compressor make any anomalousnoise?Does it

Page 212

- 28 -Model FDTVA602HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA602HESP2RFDTA301R FDCVA602HESARNominal cooling capacity(1) kW14.

Page 213 - The indoor unit PCB is

- 287 -Note (1) In models 802 and 1002, alsoreplace the power transistor.Compressor operationReplace the outdoorunit inverter PCBNormalYESNONOYESYESNO

Page 214

- 288 -(5) Inspection procedure for the failure which doesn’t have an error code(a) Louver motor does not operate Inspect at the indoor unit side

Page 215 - Check monitor

- 289 -(6) Check anomalous operation data with the wired remote controllerOperation data are recorded when there is an anomalous state and these data

Page 216 - 2. MULTI-TYPE (V MULTI)

- 290 -Romote controller signal receiving partBackup switchCheck monitor(Error code display E1~E60)Operation display light (Green) • Lights continuous

Page 217 - 2.1 GENERAL INFORMATION

- 291 -2. MULTI-TYPE (V MULTI)PACKAGED AIR-CONDITIONERCONTENTS2.1 GENERAL INFORMATION ...

Page 218 - 2.1.3 Table of models

- 292 -2.1 GENERAL INFORMATION2.1.1 Specifi c featuresIdeal for the installation in Large, single zone open Areas and L-shaped rooms, the Muliti-Type V

Page 219 - 2.2 SELECTION DATA

- 293 -2.1.3 Table of models2.1.4 Table of system combinationsNotes (1) It is possible to used different models (FDTC,FDT, FDUM, FDEN) when combin

Page 220 - Models FDTA151R, 201R, 251R

- 294 -ItemNominal cooling capacity(1)kWkWWCMMdB(A)mmNominal heating capacity(1)Power sourceNet weight Refrigerant control Starting method Outside a

Page 221 - Models FDTA301R, 401R

- 295 -ItemNominal cooling capacity(1)kWkWWCMM31 (Unit: 24 Panel: 7)dB(A)mmUnit:270 840 840Panel:35 950 950Nominal heating capacity(1)Po

Page 222 - 1. PACKAGED AIR-CONDITIONER

- 296 -Models FDTA301R, 401RItemNominal cooling capacity(1)kWkWWCMM31 (Unit:24 Panel:7)40 1dB(A)mmUnit:295 840 840Panel:35 950 950Nom

Page 223

- 2 -1. PACKAGED AIR-CONDITIONERCONTENTS1.1 GENERAL INFORMATION ...

Page 224 - Model FDTA501R

- 29 -Model FDTVA802HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA802HESP2R(7)FDTA401R FDCVA802HESARNominal cooling capacity(1) kW

Page 225 - Models FDENA151R, 201R, 251R

- 297 -Model FDTA501RItemNominal cooling capacity(1)kWkWWCMM38 (Unit:31 Panel:7)dB(A)mmUnit:365 840 840Panel:35 950 950Nominal heating

Page 226 - Models FDENA301R, 401R

- 298 -(c) Ceiling suspended type (FDEN)Models FDENA151R, 201R, 251RItemNominal cooling capacity(1)kWkWWCMM30 36dB(A)mm210 1070 690Nominal hea

Page 227 - Model FDENA501R

- 299 -Models FDENA301R, 401RItemNominal cooling capacity(1)kWkWWCMM3640 2dB(A)mm 210 1320 690Nominal heating capacity(1)Power sourceNet weig

Page 228 - Models FDKNA151R, 201R

- 300 -ItemNominal cooling capacity(1)kWkWWCMM46dB(A)mm250 1620 690Nominal heating capacity(1)Power sourceNet weight Refrigerant control Start

Page 229

- 301 -(d) Wall mounted type (FDKN)Models FDKNA151R, 201RItemNominal cooling capacity(1)kWkWWCMM12dB(A)mm298 840 240Nominal heating capacity(1

Page 230 - Wireless kit (Optional)

- 302 -Model FDKNA251RItemNominal cooling capacity(1)kWkWWCMM12dB(A)mm298 840 240Nominal heating capacity(1)Power sourceNet weight Refrigerant

Page 231 - Models FDUMA402R, 502R

- 303 -ItemkWkWWCMMkg 4034Hi: 18 Me: 16 Lo: 14 Hi: 20 Me: 18 Lo: 15Hi: 14 Me: 12 Lo: 11dB(A)mmInternal thermostat for fan motor.Frost protection

Page 232 - (2) Outdoor unit

- 304 -ItemkWkWWCMMkg 5945 1,Hi: 28 Me: 25 Lo: 22 Hi: 34 Me: 31 Lo: 2790 1dB(A)mm 350 1370 635Internal thermostat for fan motor.F

Page 233 - Model FDCVA402HENAR

- 305 -(2) Outdoor unitModel FDCVA302HENRItemkWkWkg2YC45DXD 160dB(A)WkgWCMM Cooling: 60, Heating: 48.5mm(in)mmModelFDCVA302HENR7.1 [3.5~8.0]8.1 [4

Page 234

- 306 -Model FDCVA402HENARItemkWkWkgRM-B5125MDE21 174dB(A)WkgWCMM Cooling: 75, Heating: 73mm(in)mmModelFDCVA402HENAR10.0 [6.1~11.2]11.2 [5.6~12.5]

Page 235 - Model FDCVA402HESAR

- 30 -Model FDTVA1002HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTVA1002HESP2RFDTA501R FDCVA1002HESARNominal cooling capacity(1) kW

Page 236

- 307 -Model FDCVA402HESARItemkWkWkgRM-B5125MDE31 174dB(A)WkgWCMM Cooling: 75, Heating: 73mm(in)mmModelFDCVA402HESAR10.0 [6.1~11.2]11.2 [5.6~12.5]

Page 237

- 308 -Models FDCVA502HENAR, 602HENARItemkWkWkgRM-B5125MDE21 174dB(A)WkgWCMM Cooling: 75, Heating: 73mm(in)mmModelFDCVA602HENARFDCVA502HENAR12.5 [

Page 238

- 309 -Models FDCVA502HESAR, 602HESARMotor kwItemkWkWkgRM-B5125MDE31 174dB(A)WkgWCMM Cooling: 75, Heating: 73mm(in)mmModelFDCVA602HESARFDCVA502HES

Page 239

- 310 -Model FDCVA802HESAR, 1002HESARItemkWkWkg 122 140dB(A)WkgWCMM Cooling: 150, Heating: 145mm(in)mmModelFDCVA1002HESARFDCVA802HESAR20.0 [7.0~22.4]

Page 240

- 311 -Cooling power consumptionHeating power consumptionCooling running currentHeating running currentInrush current (L.R.A)2.02/2.022.16/2.1610.4/10

Page 241

- 312 -Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONER

Page 242

- 313 - Total power factor (%) 4.78 × 1000 (Cooling) 21.1 × 220 × 100 .=. 99 % 4.58 × 1000 (Heating) 20.2× 220 × 100 .=. 99 % 2) 3 Phase modelsa)

Page 243 - Range of cooling usage

- 314 -2.2.2 Range of usage & limitationsModelItemFDCVA302~602 FDCVA802, 1002Indoor return air temperature(Upper, lower limits)Outdoor air temper

Page 244

- 315 -CoolingIndoor air W.B. temperature (˚CW.B.)Outdoor air D.B.temperature (˚CD.B.)Indoor air D.B.temperature (˚CD.B.)Range of heating usageRange o

Page 245

- 316 -In the illustration the L is main piping and ra,rb,rc, andrd are branch piping. Request(1) When the capacity of the indoor unit to be connecte

Page 246

- 31 -(c) Triple typeModel FDTVA602HENT2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDTVA602HENT2RFDTA201R FDCVA602HENARNominal cooling ca

Page 247 - 3.1 FDT series

- 317 -2.2.3 Exterior dimensionsDetails are the same as in chapter 1.2.3 see page 93.2.2.4 Inside viewDetails are the same as in chapter 1.2.4 see pag

Page 248 - Refrigerant pipes Drain pipe

- 318 - ModelModelFDT series all model(1) Wireless kit modelModel Paint colorRCN-T-35W-ER Plaster white(2) Accessories(3) Receiving outside

Page 249 - 12/N3 X Y Z

- 319 -unit: mmRefrigerant pipes Drain pipeDrain plugWireless kit backsideScrews1 Cover601715043(4) Wireless remote controller(5) Attachment of wir

Page 250 - Receivable range

- 320 -*When batteries are removed, the setting will be reset to the default setting. When batteries are removed, please follow the above procedure a

Page 251 - 3.2 FDTC • FDUM • FDU series

- 321 -Indoor unitAdress(16)(F)Indoor unitAdressRemotecontroller TerminalblockWiring of a receiver should be completed onlyfor the indoor unit that is

Page 252

- 322 -SAFETY PRECAUTIONS• Always read these “Safety Precautions” thoroughly before starting installation work.• These precautions describe important

Page 253

- 323 -CAUTION * When the battery is once removed, the setting returns to the initial setting condition (setting at factory shipping). Therefore, when

Page 254

- 324 - d) Installation with enclosed bracketUse this method when installing onto a gypsum board (7 or 18 mm), etc.1 Catch the two protrusion of th

Page 255

- 325 -(5) Wireless remote controller operation distancea) When installed on ceiling standard reception distanceReception section illuminance 300

Page 256

Air-Conditioning & Refrigeration Systems Headquarters16-5, 2-chome, Kounan, Minato-ku, Tokyo, 108-8215, JapanFax : (03) 6716-5926MULTI-TYPE (V-MUL

Page 257

- 32 -Model FDTVA602HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDTVA602HEST2RFDTA201R FDCVA602HESARNominal cooling capacity(1) kW14.

Page 258 - (d) Double twin type

- 33 -Model FDTVA802HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDTVA802HEST2RFDTA301R FDCVA802HESARNominal cooling capacity(1) kW20.

Page 259

- 34 -(d) Double twin typeModel FDTVA802HESD2R (Indoor unit: 4 units, Outdoor unit: 1 unit)ModelItemFDTVA802HESD2RFDTA201R FDCVA802HESARNominal cool

Page 260 - Model FDENVA151HEN1R

- 35 -Model FDTVA1002HESD2R (Indoor unit: 4 units, Outdoor unit: 1 unit) ModelItemFDTVA1002HESD2RFDTA251R FDCVA1002HESARNominal cooling capacity(1) k

Page 261 - Model FDENVA201HEN1R

- 36 -(3) Ceiling suspended type (FDEN)(a) Single typeModel FDENVA151HEN1RModelItemFDENVA151HEN1RFDENA151R FDCVA151HENRNominal cooling capacity(1) k

Page 262 - Model FDENVA251HEN1R

- 37 -Model FDENVA201HEN1RModelItemFDENVA201HEN1RFDENA201R FDCVA201HENRNominal cooling capacity(1) kW5.0 [2.2~5.6]Nominal heating capacity(1) kW5.4 [

Page 263

- 38 -Model FDENVA251HEN1RModelItemFDENVA251HEN1RFDENA251R FDCVA251HENRNominal cooling capacity(1) kW5.6 [2.8~6.3]Nominal heating capacity(1) kW6.7 [

Page 264 - Model FDENVA302HEN1R

- 3 -(4) Operation control function by the outdoor controller ... 166♦ Models FDCVA151 ~ 251 ...

Page 265 - Model FDENVA402HEN2R

- 39 -Model FDENVA302HEN1RModelItemFDENVA302HEN1RFDENA301R FDCVA302HENRNominal cooling capacity(1) kW7.1[3.5~8.0]Nominal heating capacity(1) kW8.0[4.

Page 266 - Model FDENVA402HES2R

- 40 -Model FDENVA402HEN2RModelItemFDENVA402HEN2RFDENA401R FDCVA402HENARNominal cooling capacity(1) kW10.0 [6.1~11.2]Nominal heating capacity(1) kW11

Page 267 - Model FDENVA502HEN2R

- 41 -Model FDENVA402HES2RModelItemFDENVA402HES2RFDENA401R FDCVA402HESARNominal cooling capacity(1) kW10.0 [6.1~11.2]Nominal heating capacity(1) kW11

Page 268 - Model FDENVA502HES2R

- 42 -Model FDENVA502HEN2RModelItemFDENVA502HEN2RFDENA501R FDCVA502HENARNominal cooling capacity(1) kW12.5 [6.5~14.0]Nominal heating capacity(1) kW14

Page 269 - Model FDENVA602HEN2R

- 43 -Model FDENVA502HES2RModelItemFDENVA502HES2RFDENA501R FDCVA502HESARNominal cooling capacity(1) kW12.5 [6.5~14.0]Nominal heating capacity(1) kW14

Page 270 - Model FDENVA602HES2R

- 44 -Model FDENVA602HEN2RModelItemFDENVA602HEN2RFDENA601R FDCVA602HENARNominal cooling capacity(1) kW14.0 [6.7~14.5]Nominal heating capacity(1) kW16

Page 271

- 45 -Model FDENVA602HES2RModelItemFDENVA602HES2RFDENA601R FDCVA602HESARNominal cooling capacity(1) kW14.0 [6.7~14.5]Nominal heating capacity(1) kW16

Page 272

- 46 -(b) Twin typeModel FDENVA302HENP1R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDENVA302HENP1RFDENA151R FDCVA302HENRNominal cooling ca

Page 273

- 47 -Model FDENVA402HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) ModelItemFDENVA402HENP2RFDENA201R FDCVA402HENARNominal cooling capacity(1) k

Page 274 - 1.1 GENERAL INFORMATION

- 48 -Model FDENVA402HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit) ModelItemFDENVA402HESP2RFDENA201R FDCVA402HESARNominal cooling capacity(1) k

Page 275

- 4 -RoHS specification : Single type(blank)P: Twin typeT: Triple typeD: Double twin typeApplicable power source ... See the specificationsHeat pump t

Page 276

- 49 -Model FDENVA502HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDENVA502HENP2RFDENA251R FDCVA502HENARNominal cooling capacity(1) kW

Page 277

- 50 -Model FDENVA502HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDENVA502HESP2RFDENA251R FDCVA502HESARNominal cooling capacity(1) kW

Page 278

- 51 -Model FDENVA602HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDENVA602HENP2RFDENA301R FDCVA602HENARNominal cooling capacity(1) kW

Page 279

- 52 -Model FDENVA602HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDENVA602HESP2RFDENA301R FDCVA602HESARNominal cooling capacity(1) kW

Page 280

- 53 -Model FDENVA802HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDENVA802HESP2RFDENA401R FDCVA802HESARNominal cooling capacity(1) kW

Page 281

- 54 -Model FDENVA1002HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDENVA1002HESP2RFDENA501R FDCVA1002HESARNominal cooling capacity(1)

Page 282

- 55 -(c) Triple typeModel FDENVA602HEN T2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDENVA602HENT2RFDENA201R FDCVA602HENARNominal coolin

Page 283

- 56 -Model FDENVA602HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDENVA602HEST2RFDENA201R FDCVA602HESARNominal cooling capacity(1) kW

Page 284 - Model FDUMVA201HEN2R

- 57 -Model FDENVA802HEST2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDENVA802HEST2RFDENA301R FDCVA802HESARNominal cooling capacity(1) kW

Page 285 - 1.2 SELECTION DATA

- 58 -(4) Satellite ducted type (FDUM)(a) single typeModel FDUMVA201HEN2RModelItemFDUMVA201HEN2RFDUMA202R FDCVA201HENRNominal cooling capacity(1) kW5

Page 286 - Model FDUMVA251HEN2R

- 5 -1.2 SELECTION DATA1.2.1 Specifications(1) Ceiling recessed compact type (FDTC)(a) Single typeModel FDTCVA151HEN1RModelItemFDTCVA151HEN1RFDTCA15

Page 287 - Model FDUMA302HEN2R

- 59 -Model FDUMVA251HEN2RModelItemFDUMVA251HEN2RFDUMA252R FDCVA251HENRNominal cooling capacity(1) kW5.6 [2.8~6.3]Nominal heating capacity(1) kW6.4 [

Page 288 - Model FDUMVA402HEN2R

- 60 -Model FDUMA302HEN2RModelItemFDUMA302HEN2RFDUMA302R FDCVA302HENRNominal cooling capacity(1) kW7.1 [3.5~8.0]Nominal heating capacity(1) kW8.0 [4.

Page 289 - Model FDUMVA402HES2R

- 61 -Model FDUMVA402HEN2RModelItemFDUMVA402HEN2RFDUMA402R FDCVA402HENARNominal cooling capacity(1) kW10.0 [6.1~11.2]Nominal heating capacity(1) kW11

Page 290 - Model FDUMVA502HEN2R

- 62 -Model FDUMVA402HES2RModelItemFDUMVA402HES2RFDUMA402R FDCVA402HESARNominal cooling capacity(1) kW10.0 [6.1~11.2]Nominal heating capacity(1) kW11

Page 291 - Model FDUMVA502HES2R

- 63 -Model FDUMVA502HEN2RModelItemFDUMVA502HEN2RFDUMA502R FDCVA502HENARNominal cooling capacity(1) kW12.5 [6.7~14.0]Nominal heating capacity(1) kW14

Page 292 - Model FDUMVA602HEN2R

- 64 -Model FDUMVA502HES2RModelItemFDUMVA502HES2RFDUMA502R FDCVA502HESARNominal cooling capacity(1) kW12.5 [6.7~14.0]Nominal heating capacity(1) kW14

Page 293 - Model FDUMVA602HES2R

- 65 -Model FDUMVA602HEN2RModelItemFDUMVA602HEN2RFDUMA602R FDCVA602HENARNominal cooling capacity(1) kW14.0 [6.7~14.5]Nominal heating capacity(1) kW16

Page 294 - (b)Twin type

- 66 -Model FDUMVA602HES2RModelItemFDUMVA602HES2RFDUMA602R FDCVA602HESARNominal cooling capacity(1) kW14.0 [6.7~14.5]Nominal heating capacity(1) kW16

Page 295

- 67 -(b)Twin typeModel FDUMVA402HENP2R(Indoor unit: 2 units, Outdoor unit: 7 units)ModelItemFDUMVA402HENP2RFDUMA202R FDCVA402HENARNominal cooling ca

Page 296 - Model FDTCVA201HEN1R

- 68 -Model FDUMVA402HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDUMVA402HESP2RFDUMA202R FDCVA402HESARNominal cooling capacity(1) kW1

Page 297

- 6 -Model FDTCVA201HEN1RModelItemFDTCVA201HEN1RFDTCA201R FDCVA201HENRNominal cooling capacity(1) kW5.0 [2.2~5.6]Nominal heating capacity(1) kW5.4 [2

Page 298

- 69 -Model FDUMVA502HENP2R(Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDUMVA502HENP2RFDUMA252R FDCVA502HENARNominal cooling capacity(1) kW1

Page 299

- 70 -Model FDUMVA502HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDUMVA502HESP2RFDUMA252R FDCVA502HESARNominal cooling capacity(1) kW1

Page 300

- 71 -Model FDUMVA602HENP2R(Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDUMVA602HENP2RFDUMA302R FDCVA602HENARNominal cooling capacity(1) kW1

Page 301

- 72 -Model FDUMVA602HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDUMVA602HESP2RFDUMA302R FDCVA602HESARNominal cooling capacity(1) kW1

Page 302

- 73 -Model FDUMVA802HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDUMVA802HESP2RFDUMA402R FDCVA802HESARNominal cooling capacity(1) kW2

Page 303

- 74 -Model FDUMVA1002HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDUMVA1002HESP2RFDUMA502R FDCVA1002HESARNominal cooling capacity(1)

Page 304

- 75 -(c) Triple typeModel FDUMVA602HENT2R(Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDUMVA602HENT2RFDUMA202R FDCVA602HENARNominal cooling

Page 305

- 76 -Model FDUMVA602HEST2R(Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDUMVA602HEST2RFDUMA202R FDCVA602HESARNominal cooling capacity(1) kW1

Page 306 - Model FDUVA802HES2R

- 77 -Model FDUMVA802HEST2R(Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDUMVA802HEST2RFDUMA302R FDCVA802HESARNominal cooling capacity(1) kW2

Page 307

- 78 -(5) High static pressure duct type (FDU)(a) Single type Model FDUVA802HES2RModelItemFDUVA802HES2R (5)FDUA801R FDCVA802HESARNominal cooling capa

Page 308 - Model FDUVA1002HES2R

- 7 -(b) Twin typeModel FDTCVA302HENP1R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTCVA302HENP1RFDTCA151R FDCVA302HENRNominal cooling cap

Page 309 - Model FDKNVA151HEN1R

- 79 - Model FDUVA1002HES2RModelItemFDUVA1002HES2R (5)FDUA1001R FDCVA1002HESARNominal cooling capacity(1) kW25.0 [10.6~28.0]Nominal heating capacity(1

Page 310 - Model FDKNVA201HEN1R

- 80 -(6) Wall mounted type (FDKN)(a) Single type Model FDKNVA151HEN1RModelItemFDKNVA151HEN1RFDKNA151R FDCVA151HENRNominal cooling capacity(1) kW4.0

Page 311 - Model FDKNVA251HEN1R

- 81 - Model FDKNVA201HEN1RModelItemFDKNVA201HEN1RFDKNA201R FDCVA201HENRNominal cooling capacity(1) kW5.0 [2.2~5.6]Nominal heating capacity(1) kW5.4 [

Page 312

- 82 - Model FDKNVA251HEN1RModelItemFDKNVA251HEN1RFDKNA251R FDCVA251HENRNominal cooling capacity(1) kW5.6 [2.8~6.0]Nominal heating capacity(1) kW6.3 [

Page 313

- 83 -(b) Twin typeModel FDKNVA302HENP1R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDKNVA302HENP1RFDKNA151R FDCVA302HENRNominal cooling ca

Page 314

- 84 -Model FDKNVA402HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDKNVA402HENP2RFDKNA201R FDCVA402HENARNominal cooling capacity(1) kW

Page 315

- 85 -Model FDKNVA402HESP2R(Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDKNVA402HESP2RFDKNA201R FDCVA402HESARNominal cooling capacity(1) kW1

Page 316

- 86 -Model FDKNVA502HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDKNVA502HENP2RFDKNA251R FDCVA502HENARNominal cooling capacity(1) kW

Page 317

- 87 -Model FDKNVA502HESP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDKNVA502HESP2RFDKNA251R FDCVA502HESARNominal cooling capacity(1) kW

Page 318

- 88 -(c) Triple typeModel FDKNVA602HENT2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDKNVA602HENT2RFDKNA201R FDCVA602HENARNominal cooling

Page 319

- 8 -Model FDTCVA402HENP2R (Indoor unit: 2 units, Outdoor unit: 1 unit)ModelItemFDTCVA402HENP2RFDTCA201R FDCVA402HENARNominal cooling capacity(1) kW1

Page 320

- 89 -Model FDKNVA602HES T2R (Indoor unit: 3 units, Outdoor unit: 1 unit)ModelItemFDKNVA602HEST2RFDKNA201R FDCVA602HESARNominal cooling capacity(1) k

Page 321

- 90 -1.2.2 Range of usage & limitationsModelsItem151, 201, 251 302~602 802, 1002Indoor return air temperature(Upper, lower limits)Refer to the s

Page 322

- 91 -CoolingIndoor air W.B. temperature (˚CW.B.)Outdoor air D.B.temperature (˚CD.B.)Indoor air D.B.temperature (˚CD.B.)Range of heating usageRange of

Page 323 - 1.2.3 Exterior dimensions

- 92 -In the illustration the L is main piping and ra,rb,rc, andrd are branch piping. Request(1) When the capacity of the indoor unit to be connected

Page 324

- 93 -1.2.3 Exterior dimensions(1) Indoor unit(a) Ceiling recessed compact type (FDTC)Models FDTCA151R, 201RVIEW AAAA14323570137197359319624845 or m

Page 325 - Model FDTA301R

- 94 -(b) Ceiling recessed type (FDT)Models FDTA151R, 201R, 251RAir supplyAir return grilleVIEW AVIEW BVIEW C VIEW DDecorative Panel700 or less(Max.

Page 326 - VIEW C VIEW D

- 95 -Air supplyAir return grilleVIEW AVIEW BVIEW C VIEW DDecorative Panel700 or less(Max. Drain lift)Hole for wiringDrain hose piece(Accessory)(Insta

Page 327 - VIEW DVIEW C

- 96 -1000or moreObstacleVIEW ADecorative PanelVIEW B2500 or more(Max. Drain lift)700 or less295~325BControl boxLiquid pipingφ9.52 (3/8")Lug fors

Page 328 - Model FDUMA202R

- 97 -HoleHole1000or moreObstacle2500 or more1471401002151406080 100218140160 1385525(Max. Drain lift)700 or less295~32542035 365187137 8402699545 or

Page 329

- 98 -(c) Satellite ducted type (FDUM)Model FDUMA202R69Space for installation and service786 (Suspension bolts pitch)Unit : mmVIEW AVIEW BLiquid pip